Fire & Smoke Dampers

The Holyoake HFS is a motorised fire, combined fire and smoke, and air/smoke/exhaust damper for rectangular ductwork. It impedes the spread of fire and smoke through ducted air systems while maintaining barrier integrity, and is compliant with the New Zealand Building Code Clause C3 and the National Construction Code of Australia.

The HFS is self-contained, spring-return actuated, and features a patented sealing system that delivers superior fire and smoke leakage performance in a single installed unit — suitable for fire duty, smoke duty, or combined fire and smoke duty.

HFS Fire Rating and Compliance

HFS fire and smoke dampers have been tested in accordance with AS 1530.4:2014 and AS 1530.7:2007, meeting the leakage integrity requirements of AS 1682.1:2015. In fire rating tests, the HFS demonstrated exceptional integrity for up to four hours, achieving a Fire Resistance Rating (FRR) of –/240/–.

Smoke leakage performance meets the ISO 10294-1 ‘S’ Classification. The HFS is compliant with the Australian National Construction Code and the NZ Building Code Clause C3.

  • Tested to AS 1530.4:2014 — up to four-hour fire rating
  • Tested to AS 1530.7:2007 — smoke leakage to AS 1682.1:2015
  • Leakage classification: ISO 10294-1 ‘S’ (smoke and leakage rated)
  • FRL/FRR: –/240/–

Sizes and Configuration

  • Single sections: up to 1,200mm (W) × 1,200mm (H)
  • Multiple sections: up to 2,400mm (W) × 2,400mm (H) in a 2×2 configuration
  • Installation in horizontal or vertical plane (specify at time of ordering)
  • Airflow and fire rated from either direction when installed in a wall

Applications

The HFS is suited to commercial, industrial, and institutional building projects where a combined fire and smoke damper is required at duct penetrations through fire-rated walls and floors. Typical applications include:

  • Supply and return duct penetrations through fire compartment walls
  • Air handling unit (AHU) connections crossing fire barriers
  • Projects requiring a single unit for both fire and smoke duty
  • High-rise commercial buildings where 4-hour fire ratings are required

Related products: IBD-FS curtain-type fire damper | LR fire and smoke damper for circular duct | HCD-ET elevated temperature smoke damper

  • Tested to AS 1530.4:2014 achieving a four hour fire rating.
  • Tested to AS 1530.7:2007 with performance requirements from AS 1682.1:2015 for smoke and air dampers.
  • Passed leakage integrity rates based on ISO 10294-1 ‘S’ Classification.
  • Single sections available up to 1200mm (wide) x 1200mm (high).
  • Multiple sections available up to 2400mm (wide) x 2400 (high) in a 2×2 configuration.
  • Multiple ducted connections are available in a multiple section damper configuration.
  • Installation permitted in both the horizontal and vertical plane (specify when ordering).
  • Airflow and fire rated from either direction when installed in a wall.
  • No penetration packing required. 
  • Multiple fire barrier solutions.